Seeing a fault code on your Slant/Fin boiler? This guide explains what the most common Slant/Fin boiler error codes mean, what’s safe to check yourself, and when to call HeatLand’s licensed, TSBC-certified gas technicians for Slant/Fin boiler repair across Metro Vancouver and the Fraser Valley.
The codes below apply across common Slant/Fin models (CHS, VSL, Sentry). Meanings follow Slant/Fin’s documented fault codes — always confirm against your unit’s own manual, because exact wording can vary by model, control board and firmware.
How to read Slant/Fin boiler error codes
CHS uses the SOLA control which displays Hold (temporary), Lockout (requires manual reset) and Alert (informational) codes as a word + number, e.g. "Lockout 67 ILK OFF" or "Hold 110 Ignition failure". VSL / VSL II uses a different control that displays lockout codes as "Loc" + number (Loc 01-37, resettable with RESET key) and permanent blocking errors as "Err" + number (Err 45-116, cannot be reset until the cause is corrected). The conventional cast-iron Sentry boiler uses a Fuel Smart HydroStat control with indicator LEDs and short text abbreviations (e.g. LCO/LWCO low-water blink) rather than numbered fault codes.
Slant/Fin boiler acting up in Metro Vancouver? HeatLand’s licensed, TSBC-certified gas technicians diagnose and repair Slant/Fin boilers across Greater Vancouver — including units we didn’t install.
Call (604) 330-3812Get a free repair estimateNo heat? Emergency repairSlant/Fin boiler error codes & what they mean
These are the Slant/Fin boiler codes our Greater Vancouver technicians see most. Anything marked pro repair involves gas, electrical, sealed-combustion or control-board work that must be done by a licensed gas technician (TSBC-certified in BC) — never open gas or electrical components yourself.
| Code | What it usually means | Common causes | Safe to check yourself |
|---|---|---|---|
| Lockout 2 | Waiting for safety data verification (CHS / SOLA control internal startup fault) pro repair | Faulty SOLA controller | Confirm the boiler has power; Try one single reset using the controller reset button |
| Hold 27 | Flame sensor shorted to ground detected (a flame circuit short can show up as a flame circuit timeout) pro repair | Condensate drain blocked; External voltage applied to R & CH terminals; 4-20mA input current too high (over 21mA) | Check that the condensate drain line and trap are not blocked or frozen and that condensate is flowing out; Try one single reset |
| Hold 61 | Anti short-cycle delay active (normal operation; burner is waiting out a timer) DIY-checkable | Normal operation – the control is enforcing a minimum off-time between burner cycles | No action usually needed – allow the timer to expire and the burner will resume |
| Hold 62 | Fan (blower) speed not proved pro repair | Normal momentarily before ignition (Drive to Lightoff); Blown fuse A preventing blower operation; Blower wiring/connector defect | Confirm the boiler has power; Try one single reset |
| Hold 67 | ILK OFF – interlock open (commonly a low-water condition or an open external limit wired to LIM) pro repair | Low water condition in the boiler; Internal low-water cut-off (LWCO) tripped; External limit device (wired to LIM) is open | Check the boiler system pressure gauge – low pressure can indicate low water; Try one single reset; if it returns, call a technician |
| Lockout or Hold 79 | Outlet high limit – boiler outlet water temperature exceeded the high-limit setpoint (factory 200F / 93C) pro repair | CH or DHW setpoint plus hysteresis exceeds the high-limit setpoint; CH or DHW pump problem / insufficient flow; Incorrect outlet high limit or high-limit response setting | Check that the heating system has adequate water pressure on the gauge; Confirm the thermostat is not calling for an unreasonably high temperature; Try one single reset |
| Lockout or Hold 81 | Delta-T limit – temperature rise across the boiler too high (often accompanied by banging or hissing), indicating insufficient water flow pro repair | Insufficient water flow; Blown fuse B; Appliance (boiler) pump problem | Check that water pressure on the gauge is at least 15 PSI; Try one single reset |
| Lockout 82 | Stack limit – flue/stack exhaust gas temperature exceeded the stack high-limit setpoint pro repair | Dirty heat exchanger / combustion chamber; Incorrect stack limit setpoint | Try one single reset; if it returns, the boiler needs cleaning/service |
| Lockout 85 | Inlet/Outlet inversion limit – inlet and outlet temperatures are inverted (pump flowing in the wrong direction) pro repair | Pump installed/flowing in the wrong direction | No safe homeowner action – this is an installation/flow-direction issue for a technician |
| Lockout or Hold 88 | Outlet T-Rise limit – rate of outlet temperature rise too fast, indicating insufficient water flow pro repair | Insufficient water flow (same causes as Delta-T limit / Lockout 81) | Check that water pressure on the gauge is at least 15 PSI; Try one single reset |
| Hold 91 | Inlet sensor fault – boiler inlet (return) temperature sensor reading invalid pro repair | Sensor disconnected; Faulty sensor | No safe homeowner action – sensor diagnosis requires opening the unit; call a technician |
| Hold 92 | Outlet sensor fault – boiler outlet (supply) temperature sensor reading invalid pro repair | Sensor disconnected; Faulty sensor | No safe homeowner action – sensor diagnosis requires opening the unit; call a technician |
| Hold 95 | Stack sensor fault – flue/stack temperature sensor reading invalid pro repair | Sensor disconnected; Faulty sensor | No safe homeowner action – sensor diagnosis requires opening the unit; call a technician |
| Lockout 109 or Hold 110 | Ignition failure – failure to prove flame after 3 (CHS) ignition attempts pro repair | Manual gas shutoff valve closed / insufficient gas pressure; Spark cable or flame rod disconnected; Blocked venting / air-inlet | Confirm the gas supply is turned on and other gas appliances work; Confirm the boiler has power; Try one single reset; if it fails again, call a technician |
| Lockout 113 | Flame circuit timeout (a flame circuit shorted to ground can show up as Lockout 113) pro repair | Condensate drain blocked; Voltage applied to R & CH terminals; 4-20mA input current too high (over 21mA) | Check that the condensate drain line and trap are not blocked or frozen; Try one single reset |
| Lockout 122 | Light-off rate proving failed – blower did not reach/prove the correct light-off speed pro repair | Blower not turning on; Missing or incorrect blower feedback signal; Blower stuck always on | Confirm the boiler has power; Try one single reset |
| Lockout 138 | Flame too low – flame signal below the required threshold during operation pro repair | Blocked venting / air-inlet; Fouled or faulty flame sensor | Try one single reset; if it returns, the unit needs service |
| Lockout 174 | Safety relay feedback incorrect (often a failing limit switch in the ILK / interlock circuit) pro repair | Failing limit switch in the ILK circuit (internal LWCO or external limit between R and LIM); Hardware failure of the SOLA controller | Check the boiler system pressure gauge (low water can trip the LWCO); Try one single reset |
| Alert 248 | CH outdoor temperature was invalid – outdoor reset sensor not detected (informational alert, not a lockout) DIY-checkable | Outdoor sensor not connected (the CHS is factory-shipped with Outdoor Reset enabled) | No action needed for heating to run; have a technician connect an outdoor sensor or disable outdoor reset |
| Loc 01 | No flame detected after five ignition attempts pro repair | Incorrect gas supply pressure; No ignition spark / wrong electrode position or gap; Insufficient gas | Confirm the gas supply is turned on and other gas appliances work; Confirm the boiler has power; Press the RESET key once; if it fails again, call a technician |
| Loc 02 | Gas valve not supplied before ignition try (a safety-chain / limit device is open) pro repair | Low-water cut-off (LWCO) open; Flue blocked pressure switch open; High-limit temperature switch open | Check the boiler system pressure gauge for low water/low pressure; Press the RESET key once; if it returns, call a technician |
| Loc 03 | Gas valve lost cable connection during firing pro repair | Interrupted wiring between gas valve and control board; Faulty gas valve or control board | Press the RESET key once; if it returns, call a technician |
| Loc 04 | Gas valve relay not closing pro repair | Interrupted wiring between gas valve and control board; Faulty gas valve or control board | Press the RESET key once; if it returns, call a technician |
| Loc 05 | Gas valve circuit fault (a safety-chain / limit device is open) pro repair | Low-water cut-off (LWCO) open; Flue blocked pressure switch open; High-limit temperature switch open | Check the boiler system pressure gauge for low water/low pressure; Press the RESET key once; if it returns, call a technician |
| Loc 06 | Safety relay open error pro repair | Power control board fault | Press the RESET key once; if it returns, call a technician |
| Loc 07 | Safety relay closed error pro repair | Power control board fault | Press the RESET key once; if it returns, call a technician |
| Loc 11 | Blocking error active for over 20 hours (the underlying blocking 'Err' must be read and resolved) pro repair | A blocking error condition has persisted; press RESET to see the underlying blocking-error reference | Press the RESET key once; if it returns, call a technician to read and resolve the underlying error |
| Loc 12 | Fan (blower) error pro repair | No 120VAC power to the fan; No PWM control signal to the fan; Faulty fan | Confirm the boiler has power; Press the RESET key once; if it returns, call a technician |
| Loc 27 | Flame present with closed gas valve pro repair | Gas valve not fully closing (gas valve fault) | No safe homeowner action – this is a gas-valve safety fault; turn off and call a technician |
| Loc 28 | Flame present with closed gas valve pro repair | Gas valve not fully closing (gas valve fault) | No safe homeowner action – this is a gas-valve safety fault; turn off and call a technician |
| Loc 31 | Flame lost five times during one heat demand pro repair | Faulty flame detection electrode; Obstruction on air inlet / flue exhaust system; Air-inlet contamination from combustion gas (flue terminal too close to air-inlet terminal) | Visually check that the outside air-inlet and exhaust terminals are clear of snow, leaves or debris; Press the RESET key once; if it returns, call a technician |
| Err 54 | Flame detected in a state in which no flame is allowed to be seen (blocking error – permanent) pro repair | Power control board fault | No safe homeowner action – this is a permanent blocking error; call a technician |
| Err 55 / 56 / 57 / 58 / 59 | Low water pressure error (blocking error) pro repair | Low water/pressure in the heating system; Faulty pressure sensor | Check the system pressure gauge – if low, a technician can top up the system to the correct pressure; No homeowner action beyond checking the gauge |
| Err 60 | High flue gas temperature error (blocking error) pro repair | Combustion efficiency lower than 88% (flue gas / water side of heat exchanger fouled); Faulty flue gas temperature sensor | No safe homeowner action – the unit needs cleaning/service; call a technician |
| Err 61 | Return temperature higher than supply (burning) temperature – sensor fault pro repair | Temperature sensor out of specification / faulty | No safe homeowner action – sensor diagnosis is a technician task |
| Err 64 | No correct frequency signal, no correct ground connection, or no communication with the watchdog pro repair | Supply frequency out of the 55-65 Hz range; Improper ground connection; Power control board fault | Confirm the boiler has power; this is an electrical-supply/grounding issue for a technician or electrician |
| Err 65 | Hot/neutral reversed – supply voltage polarity reversed pro repair | Line and neutral wires reversed at the supply | No safe homeowner action – reversed polarity must be corrected by a technician or electrician |
| Err 67 | Faulty earth (ground) connection pro repair | Missing or poor earth/ground connection to the appliance | No safe homeowner action – grounding must be corrected by a technician or electrician |
| Err 72 / 73 / 76 | Supply / return / DHW temperature sensor open circuit (blocking error) pro repair | Temperature sensor disconnected or out of specification | No safe homeowner action – sensor diagnosis is a technician task |
| Err 80 / 81 / 84 / 86 | Supply / return / DHW / flue temperature sensor shorted (blocking error) pro repair | Temperature sensor shorted or out of specification | No safe homeowner action – sensor diagnosis is a technician task |
| Err 87 | Reset button error – too many reset presses within 60 seconds DIY-checkable | Reset key pressed too many times in a short period | Stop pressing reset; wait, then try a single reset only. If a fault keeps returning, call a technician instead of repeatedly resetting |
| Err 93 | Appliance selection error – control configured for the wrong boiler model pro repair | Incorrect appliance configuration parameter (3000-series parameter) | No safe homeowner action – configuration must be corrected by a technician |
| Err 114 | Too low water flow pro repair | Insufficient water flow through the system; Obstruction in the water system | Check the system pressure gauge for adequate pressure; No further homeowner action – flow problems are a technician task |
| Err 115 | Cascade – boiler master failure pro repair | Master (manager) boiler fault in a multi-boiler cascade system | No safe homeowner action – cascade systems must be serviced by a technician |
| Err 116 | Cascade communication failure pro repair | Bus communication interrupted between cascaded boilers; A cascaded boiler is not working | No safe homeowner action – cascade systems must be serviced by a technician |
| LWCO / LOW WATER (red light blinking) | Low-water cut-off has locked out the burner (Sentry HydroStat control) – shown as a blinking red Low Water light, not a numbered code pro repair | Low water level in the boiler; Low-water cut-off condition sustained for 30 seconds (manual-reset LWCO mode locks out the burner) | Check the boiler system pressure gauge for low pressure / low water; Do NOT add water until the boiler has fully cooled, and have a qualified heating professional check the system before resuming operation |
Slant/Fin boiler codes we get called for most
Lockout 109 or Hold 110 — Ignition failure – failure to prove flame after 3 (CHS) ignition attempts
Typical causes include manual gas shutoff valve closed / insufficient gas pressure; spark cable or flame rod disconnected; blocked venting / air-inlet. A few things are safe to check yourself (Confirm the gas supply is turned on and other gas appliances work; Confirm the boiler has power), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes Lockout 109 or Hold 110 on Slant/Fin boilers throughout Greater Vancouver.
Loc 31 — Flame lost five times during one heat demand
Typical causes include faulty flame detection electrode; obstruction on air inlet / flue exhaust system; air-inlet contamination from combustion gas (flue terminal too close to air-inlet terminal). A few things are safe to check yourself (Visually check that the outside air-inlet and exhaust terminals are clear of snow, leaves or debris; Press the RESET key once; if it returns, call a technician), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes Loc 31 on Slant/Fin boilers throughout Greater Vancouver.
Err 55 / 56 / 57 / 58 / 59 — Low water pressure error (blocking error)
Typical causes include low water/pressure in the heating system; faulty pressure sensor. A few things are safe to check yourself (Check the system pressure gauge – if low, a technician can top up the system to the correct pressure; No homeowner action beyond checking the gauge), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes Err 55 / 56 / 57 / 58 / 59 on Slant/Fin boilers throughout Greater Vancouver.
Lockout or Hold 79 — Outlet high limit – boiler outlet water temperature exceeded the high-limit setpoint (factory 200F / 93C)
Typical causes include ch or dhw setpoint plus hysteresis exceeds the high-limit setpoint; ch or dhw pump problem / insufficient flow; incorrect outlet high limit or high-limit response setting. A few things are safe to check yourself (Check that the heating system has adequate water pressure on the gauge; Confirm the thermostat is not calling for an unreasonably high temperature), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes Lockout or Hold 79 on Slant/Fin boilers throughout Greater Vancouver.
Is it safe to keep running a Slant/Fin boiler with a fault code?
Most Slant/Fin fault codes put the boiler into a safe lockout for a reason. You can safely check the basics — gas supply on, power on, the thermostat calling for heat, system pressure in the normal range, and the condensate drain not frozen or blocked (a common cause in Vancouver cold snaps) — and restart it once. If the code returns, stop and book a technician. If you ever smell gas, leave the building and call your gas utility’s emergency line or 911 first. If a carbon-monoxide alarm sounds, get everyone out and call 911.
Slant/Fin boiler repair across Greater Vancouver
HeatLand has kept Metro Vancouver homes comfortable since 1999. Our licensed, insured technicians diagnose and repair Slant/Fin boilers — ignition faults, flame and sensor errors, low-pressure and pump problems, fan and flue faults, and control-board issues — including units we didn’t install. We’re brand-agnostic, carry common parts, and give you an honest repair-or-replace assessment with upfront pricing and a free estimate. If your boiler is beyond economical repair, we’ll show you right-sized, high-efficiency replacement options and the rebates available.
Need it sorted fast? We offer priority emergency boiler repair. Explore Boiler services, browse all boiler error codes by brand, or request a free estimate.
Slant/Fin boiler service areas
We repair Slant/Fin boilers across Greater Vancouver and the Fraser Valley, including:
Slant/Fin boiler error code FAQs
Can I reset my Slant/Fin boiler myself?
Yes — power-cycling the reset button once is generally safe after you’ve checked the basics (gas supply on, power on, the thermostat calling for heat, system pressure in the normal range, and the condensate drain not frozen or blocked (a common cause in Vancouver cold snaps)). If the boiler faults again right away, stop and note the code — repeatedly resetting a boiler that keeps locking out can mask a real problem. Call a licensed, TSBC-certified gas technician to diagnose it.
What does the Slant/Fin Hold 27 code mean?
On Slant/Fin boilers, Hold 27 commonly indicates flame sensor shorted to ground detected (a flame circuit short can show up as a flame circuit timeout). Confirm the exact meaning against your unit’s manual — codes can vary by model and series — and have the repair done by a licensed, TSBC-certified gas technician. HeatLand fixes this across Greater Vancouver.
Do you repair Slant/Fin boilers you didn’t install?
Yes. HeatLand is brand-agnostic and services Slant/Fin boilers throughout Metro Vancouver and the Fraser Valley, whether or not we installed the unit. We carry common parts and give you an honest repair-or-replace assessment.
Is a Slant/Fin boiler fault code an emergency?
No heat in cold weather is worth treating urgently. If you ever smell gas, leave the building and call your gas utility’s emergency line or 911 first. If a carbon-monoxide alarm sounds, get everyone out and call 911. For priority boiler repair across Greater Vancouver, call (604) 330-3812.
How much does Slant/Fin boiler repair cost in Vancouver?
It depends on the fault. Many Slant/Fin codes point to sensors, ignition or pump parts — usually far cheaper than replacement. We give upfront pricing and a free estimate before any work.
Slant/Fin boiler acting up in Metro Vancouver? HeatLand’s licensed, TSBC-certified gas technicians diagnose and repair Slant/Fin boilers across Greater Vancouver — including units we didn’t install.
Call (604) 330-3812Get a free repair estimateNo heat? Emergency repairMore Boiler error-code guides
HeatLand repairs every major boiler brand across Greater Vancouver. More brand guides:
Laars boiler codes
59 Laars boiler fault codes — meanings, causes & repair.
Burnham boiler codes
48 Burnham boiler fault codes — meanings, causes & repair.
Triangle Tube boiler codes
46 Triangle Tube boiler fault codes — meanings, causes & repair.
Rinnai boiler codes
44 Rinnai boiler fault codes — meanings, causes & repair.
Buderus boiler codes
41 Buderus boiler fault codes — meanings, causes & repair.
IBC boiler codes
40 IBC boiler fault codes — meanings, causes & repair.