Slant/Fin Boiler Error Codes — Meanings, Causes & Repair in Greater Vancouver

Slant/Fin Boiler Error Codes — Meanings, Causes & Repair in Greater Vancouver

Seeing a fault code on your Slant/Fin boiler? This guide explains what the most common Slant/Fin boiler error codes mean, what’s safe to check yourself, and when to call HeatLand’s licensed, TSBC-certified gas technicians for Slant/Fin boiler repair across Metro Vancouver and the Fraser Valley.

The codes below apply across common Slant/Fin models (CHS, VSL, Sentry). Meanings follow Slant/Fin’s documented fault codes — always confirm against your unit’s own manual, because exact wording can vary by model, control board and firmware.

How to read Slant/Fin boiler error codes

CHS uses the SOLA control which displays Hold (temporary), Lockout (requires manual reset) and Alert (informational) codes as a word + number, e.g. "Lockout 67 ILK OFF" or "Hold 110 Ignition failure". VSL / VSL II uses a different control that displays lockout codes as "Loc" + number (Loc 01-37, resettable with RESET key) and permanent blocking errors as "Err" + number (Err 45-116, cannot be reset until the cause is corrected). The conventional cast-iron Sentry boiler uses a Fuel Smart HydroStat control with indicator LEDs and short text abbreviations (e.g. LCO/LWCO low-water blink) rather than numbered fault codes.

Slant/Fin boiler acting up in Metro Vancouver? HeatLand’s licensed, TSBC-certified gas technicians diagnose and repair Slant/Fin boilers across Greater Vancouver — including units we didn’t install.

Call (604) 330-3812Get a free repair estimateNo heat? Emergency repair

Slant/Fin boiler error codes & what they mean

These are the Slant/Fin boiler codes our Greater Vancouver technicians see most. Anything marked pro repair involves gas, electrical, sealed-combustion or control-board work that must be done by a licensed gas technician (TSBC-certified in BC) — never open gas or electrical components yourself.

CodeWhat it usually meansCommon causesSafe to check yourself
Lockout 2Waiting for safety data verification (CHS / SOLA control internal startup fault) pro repairFaulty SOLA controllerConfirm the boiler has power; Try one single reset using the controller reset button
Hold 27Flame sensor shorted to ground detected (a flame circuit short can show up as a flame circuit timeout) pro repairCondensate drain blocked; External voltage applied to R & CH terminals; 4-20mA input current too high (over 21mA)Check that the condensate drain line and trap are not blocked or frozen and that condensate is flowing out; Try one single reset
Hold 61Anti short-cycle delay active (normal operation; burner is waiting out a timer) DIY-checkableNormal operation – the control is enforcing a minimum off-time between burner cyclesNo action usually needed – allow the timer to expire and the burner will resume
Hold 62Fan (blower) speed not proved pro repairNormal momentarily before ignition (Drive to Lightoff); Blown fuse A preventing blower operation; Blower wiring/connector defectConfirm the boiler has power; Try one single reset
Hold 67ILK OFF – interlock open (commonly a low-water condition or an open external limit wired to LIM) pro repairLow water condition in the boiler; Internal low-water cut-off (LWCO) tripped; External limit device (wired to LIM) is openCheck the boiler system pressure gauge – low pressure can indicate low water; Try one single reset; if it returns, call a technician
Lockout or Hold 79Outlet high limit – boiler outlet water temperature exceeded the high-limit setpoint (factory 200F / 93C) pro repairCH or DHW setpoint plus hysteresis exceeds the high-limit setpoint; CH or DHW pump problem / insufficient flow; Incorrect outlet high limit or high-limit response settingCheck that the heating system has adequate water pressure on the gauge; Confirm the thermostat is not calling for an unreasonably high temperature; Try one single reset
Lockout or Hold 81Delta-T limit – temperature rise across the boiler too high (often accompanied by banging or hissing), indicating insufficient water flow pro repairInsufficient water flow; Blown fuse B; Appliance (boiler) pump problemCheck that water pressure on the gauge is at least 15 PSI; Try one single reset
Lockout 82Stack limit – flue/stack exhaust gas temperature exceeded the stack high-limit setpoint pro repairDirty heat exchanger / combustion chamber; Incorrect stack limit setpointTry one single reset; if it returns, the boiler needs cleaning/service
Lockout 85Inlet/Outlet inversion limit – inlet and outlet temperatures are inverted (pump flowing in the wrong direction) pro repairPump installed/flowing in the wrong directionNo safe homeowner action – this is an installation/flow-direction issue for a technician
Lockout or Hold 88Outlet T-Rise limit – rate of outlet temperature rise too fast, indicating insufficient water flow pro repairInsufficient water flow (same causes as Delta-T limit / Lockout 81)Check that water pressure on the gauge is at least 15 PSI; Try one single reset
Hold 91Inlet sensor fault – boiler inlet (return) temperature sensor reading invalid pro repairSensor disconnected; Faulty sensorNo safe homeowner action – sensor diagnosis requires opening the unit; call a technician
Hold 92Outlet sensor fault – boiler outlet (supply) temperature sensor reading invalid pro repairSensor disconnected; Faulty sensorNo safe homeowner action – sensor diagnosis requires opening the unit; call a technician
Hold 95Stack sensor fault – flue/stack temperature sensor reading invalid pro repairSensor disconnected; Faulty sensorNo safe homeowner action – sensor diagnosis requires opening the unit; call a technician
Lockout 109 or Hold 110Ignition failure – failure to prove flame after 3 (CHS) ignition attempts pro repairManual gas shutoff valve closed / insufficient gas pressure; Spark cable or flame rod disconnected; Blocked venting / air-inletConfirm the gas supply is turned on and other gas appliances work; Confirm the boiler has power; Try one single reset; if it fails again, call a technician
Lockout 113Flame circuit timeout (a flame circuit shorted to ground can show up as Lockout 113) pro repairCondensate drain blocked; Voltage applied to R & CH terminals; 4-20mA input current too high (over 21mA)Check that the condensate drain line and trap are not blocked or frozen; Try one single reset
Lockout 122Light-off rate proving failed – blower did not reach/prove the correct light-off speed pro repairBlower not turning on; Missing or incorrect blower feedback signal; Blower stuck always onConfirm the boiler has power; Try one single reset
Lockout 138Flame too low – flame signal below the required threshold during operation pro repairBlocked venting / air-inlet; Fouled or faulty flame sensorTry one single reset; if it returns, the unit needs service
Lockout 174Safety relay feedback incorrect (often a failing limit switch in the ILK / interlock circuit) pro repairFailing limit switch in the ILK circuit (internal LWCO or external limit between R and LIM); Hardware failure of the SOLA controllerCheck the boiler system pressure gauge (low water can trip the LWCO); Try one single reset
Alert 248CH outdoor temperature was invalid – outdoor reset sensor not detected (informational alert, not a lockout) DIY-checkableOutdoor sensor not connected (the CHS is factory-shipped with Outdoor Reset enabled)No action needed for heating to run; have a technician connect an outdoor sensor or disable outdoor reset
Loc 01No flame detected after five ignition attempts pro repairIncorrect gas supply pressure; No ignition spark / wrong electrode position or gap; Insufficient gasConfirm the gas supply is turned on and other gas appliances work; Confirm the boiler has power; Press the RESET key once; if it fails again, call a technician
Loc 02Gas valve not supplied before ignition try (a safety-chain / limit device is open) pro repairLow-water cut-off (LWCO) open; Flue blocked pressure switch open; High-limit temperature switch openCheck the boiler system pressure gauge for low water/low pressure; Press the RESET key once; if it returns, call a technician
Loc 03Gas valve lost cable connection during firing pro repairInterrupted wiring between gas valve and control board; Faulty gas valve or control boardPress the RESET key once; if it returns, call a technician
Loc 04Gas valve relay not closing pro repairInterrupted wiring between gas valve and control board; Faulty gas valve or control boardPress the RESET key once; if it returns, call a technician
Loc 05Gas valve circuit fault (a safety-chain / limit device is open) pro repairLow-water cut-off (LWCO) open; Flue blocked pressure switch open; High-limit temperature switch openCheck the boiler system pressure gauge for low water/low pressure; Press the RESET key once; if it returns, call a technician
Loc 06Safety relay open error pro repairPower control board faultPress the RESET key once; if it returns, call a technician
Loc 07Safety relay closed error pro repairPower control board faultPress the RESET key once; if it returns, call a technician
Loc 11Blocking error active for over 20 hours (the underlying blocking 'Err' must be read and resolved) pro repairA blocking error condition has persisted; press RESET to see the underlying blocking-error referencePress the RESET key once; if it returns, call a technician to read and resolve the underlying error
Loc 12Fan (blower) error pro repairNo 120VAC power to the fan; No PWM control signal to the fan; Faulty fanConfirm the boiler has power; Press the RESET key once; if it returns, call a technician
Loc 27Flame present with closed gas valve pro repairGas valve not fully closing (gas valve fault)No safe homeowner action – this is a gas-valve safety fault; turn off and call a technician
Loc 28Flame present with closed gas valve pro repairGas valve not fully closing (gas valve fault)No safe homeowner action – this is a gas-valve safety fault; turn off and call a technician
Loc 31Flame lost five times during one heat demand pro repairFaulty flame detection electrode; Obstruction on air inlet / flue exhaust system; Air-inlet contamination from combustion gas (flue terminal too close to air-inlet terminal)Visually check that the outside air-inlet and exhaust terminals are clear of snow, leaves or debris; Press the RESET key once; if it returns, call a technician
Err 54Flame detected in a state in which no flame is allowed to be seen (blocking error – permanent) pro repairPower control board faultNo safe homeowner action – this is a permanent blocking error; call a technician
Err 55 / 56 / 57 / 58 / 59Low water pressure error (blocking error) pro repairLow water/pressure in the heating system; Faulty pressure sensorCheck the system pressure gauge – if low, a technician can top up the system to the correct pressure; No homeowner action beyond checking the gauge
Err 60High flue gas temperature error (blocking error) pro repairCombustion efficiency lower than 88% (flue gas / water side of heat exchanger fouled); Faulty flue gas temperature sensorNo safe homeowner action – the unit needs cleaning/service; call a technician
Err 61Return temperature higher than supply (burning) temperature – sensor fault pro repairTemperature sensor out of specification / faultyNo safe homeowner action – sensor diagnosis is a technician task
Err 64No correct frequency signal, no correct ground connection, or no communication with the watchdog pro repairSupply frequency out of the 55-65 Hz range; Improper ground connection; Power control board faultConfirm the boiler has power; this is an electrical-supply/grounding issue for a technician or electrician
Err 65Hot/neutral reversed – supply voltage polarity reversed pro repairLine and neutral wires reversed at the supplyNo safe homeowner action – reversed polarity must be corrected by a technician or electrician
Err 67Faulty earth (ground) connection pro repairMissing or poor earth/ground connection to the applianceNo safe homeowner action – grounding must be corrected by a technician or electrician
Err 72 / 73 / 76Supply / return / DHW temperature sensor open circuit (blocking error) pro repairTemperature sensor disconnected or out of specificationNo safe homeowner action – sensor diagnosis is a technician task
Err 80 / 81 / 84 / 86Supply / return / DHW / flue temperature sensor shorted (blocking error) pro repairTemperature sensor shorted or out of specificationNo safe homeowner action – sensor diagnosis is a technician task
Err 87Reset button error – too many reset presses within 60 seconds DIY-checkableReset key pressed too many times in a short periodStop pressing reset; wait, then try a single reset only. If a fault keeps returning, call a technician instead of repeatedly resetting
Err 93Appliance selection error – control configured for the wrong boiler model pro repairIncorrect appliance configuration parameter (3000-series parameter)No safe homeowner action – configuration must be corrected by a technician
Err 114Too low water flow pro repairInsufficient water flow through the system; Obstruction in the water systemCheck the system pressure gauge for adequate pressure; No further homeowner action – flow problems are a technician task
Err 115Cascade – boiler master failure pro repairMaster (manager) boiler fault in a multi-boiler cascade systemNo safe homeowner action – cascade systems must be serviced by a technician
Err 116Cascade communication failure pro repairBus communication interrupted between cascaded boilers; A cascaded boiler is not workingNo safe homeowner action – cascade systems must be serviced by a technician
LWCO / LOW WATER (red light blinking)Low-water cut-off has locked out the burner (Sentry HydroStat control) – shown as a blinking red Low Water light, not a numbered code pro repairLow water level in the boiler; Low-water cut-off condition sustained for 30 seconds (manual-reset LWCO mode locks out the burner)Check the boiler system pressure gauge for low pressure / low water; Do NOT add water until the boiler has fully cooled, and have a qualified heating professional check the system before resuming operation

Slant/Fin boiler codes we get called for most

Lockout 109 or Hold 110 — Ignition failure – failure to prove flame after 3 (CHS) ignition attempts

Typical causes include manual gas shutoff valve closed / insufficient gas pressure; spark cable or flame rod disconnected; blocked venting / air-inlet. A few things are safe to check yourself (Confirm the gas supply is turned on and other gas appliances work; Confirm the boiler has power), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes Lockout 109 or Hold 110 on Slant/Fin boilers throughout Greater Vancouver.

Loc 31 — Flame lost five times during one heat demand

Typical causes include faulty flame detection electrode; obstruction on air inlet / flue exhaust system; air-inlet contamination from combustion gas (flue terminal too close to air-inlet terminal). A few things are safe to check yourself (Visually check that the outside air-inlet and exhaust terminals are clear of snow, leaves or debris; Press the RESET key once; if it returns, call a technician), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes Loc 31 on Slant/Fin boilers throughout Greater Vancouver.

Err 55 / 56 / 57 / 58 / 59 — Low water pressure error (blocking error)

Typical causes include low water/pressure in the heating system; faulty pressure sensor. A few things are safe to check yourself (Check the system pressure gauge – if low, a technician can top up the system to the correct pressure; No homeowner action beyond checking the gauge), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes Err 55 / 56 / 57 / 58 / 59 on Slant/Fin boilers throughout Greater Vancouver.

Lockout or Hold 79 — Outlet high limit – boiler outlet water temperature exceeded the high-limit setpoint (factory 200F / 93C)

Typical causes include ch or dhw setpoint plus hysteresis exceeds the high-limit setpoint; ch or dhw pump problem / insufficient flow; incorrect outlet high limit or high-limit response setting. A few things are safe to check yourself (Check that the heating system has adequate water pressure on the gauge; Confirm the thermostat is not calling for an unreasonably high temperature), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes Lockout or Hold 79 on Slant/Fin boilers throughout Greater Vancouver.

Is it safe to keep running a Slant/Fin boiler with a fault code?

Most Slant/Fin fault codes put the boiler into a safe lockout for a reason. You can safely check the basics — gas supply on, power on, the thermostat calling for heat, system pressure in the normal range, and the condensate drain not frozen or blocked (a common cause in Vancouver cold snaps) — and restart it once. If the code returns, stop and book a technician. If you ever smell gas, leave the building and call your gas utility’s emergency line or 911 first. If a carbon-monoxide alarm sounds, get everyone out and call 911.

Slant/Fin boiler repair across Greater Vancouver

HeatLand has kept Metro Vancouver homes comfortable since 1999. Our licensed, insured technicians diagnose and repair Slant/Fin boilers — ignition faults, flame and sensor errors, low-pressure and pump problems, fan and flue faults, and control-board issues — including units we didn’t install. We’re brand-agnostic, carry common parts, and give you an honest repair-or-replace assessment with upfront pricing and a free estimate. If your boiler is beyond economical repair, we’ll show you right-sized, high-efficiency replacement options and the rebates available.

Need it sorted fast? We offer priority emergency boiler repair. Explore Boiler services, browse all boiler error codes by brand, or request a free estimate.

Slant/Fin boiler service areas

We repair Slant/Fin boilers across Greater Vancouver and the Fraser Valley, including:

VancouverBurnabySurreyRichmondCoquitlamNorth VancouverWest VancouverNew WestminsterLangleyDeltaPort CoquitlamPort MoodyMaple RidgeWhite RockAbbotsfordChilliwack

Slant/Fin boiler error code FAQs

Can I reset my Slant/Fin boiler myself?

Yes — power-cycling the reset button once is generally safe after you’ve checked the basics (gas supply on, power on, the thermostat calling for heat, system pressure in the normal range, and the condensate drain not frozen or blocked (a common cause in Vancouver cold snaps)). If the boiler faults again right away, stop and note the code — repeatedly resetting a boiler that keeps locking out can mask a real problem. Call a licensed, TSBC-certified gas technician to diagnose it.

What does the Slant/Fin Hold 27 code mean?

On Slant/Fin boilers, Hold 27 commonly indicates flame sensor shorted to ground detected (a flame circuit short can show up as a flame circuit timeout). Confirm the exact meaning against your unit’s manual — codes can vary by model and series — and have the repair done by a licensed, TSBC-certified gas technician. HeatLand fixes this across Greater Vancouver.

Do you repair Slant/Fin boilers you didn’t install?

Yes. HeatLand is brand-agnostic and services Slant/Fin boilers throughout Metro Vancouver and the Fraser Valley, whether or not we installed the unit. We carry common parts and give you an honest repair-or-replace assessment.

Is a Slant/Fin boiler fault code an emergency?

No heat in cold weather is worth treating urgently. If you ever smell gas, leave the building and call your gas utility’s emergency line or 911 first. If a carbon-monoxide alarm sounds, get everyone out and call 911. For priority boiler repair across Greater Vancouver, call (604) 330-3812.

How much does Slant/Fin boiler repair cost in Vancouver?

It depends on the fault. Many Slant/Fin codes point to sensors, ignition or pump parts — usually far cheaper than replacement. We give upfront pricing and a free estimate before any work.

Slant/Fin boiler acting up in Metro Vancouver? HeatLand’s licensed, TSBC-certified gas technicians diagnose and repair Slant/Fin boilers across Greater Vancouver — including units we didn’t install.

Call (604) 330-3812Get a free repair estimateNo heat? Emergency repair

More Boiler error-code guides

HeatLand repairs every major boiler brand across Greater Vancouver. More brand guides:

Get your free estimate

Tell us what's going on and we'll get right back to you — no pressure, no obligation.

  • Free, no-obligation quotes
  • All major brands serviced
  • Metro Vancouver & the Fraser Valley
  • Financing & CleanBC rebate help
Prefer to talk now? Call (604) 330-3812

We'll only use your details to contact you about your request.