Seeing a fault code on your Burnham boiler? This guide explains what the most common Burnham boiler error codes mean, what’s safe to check yourself, and when to call HeatLand’s licensed, TSBC-certified gas technicians for Burnham boiler repair across Metro Vancouver and the Fraser Valley.

The codes below apply across common Burnham models (Alpine, K2, Aspen, ESC). Meanings follow Burnham’s documented fault codes — always confirm against your unit’s own manual, because exact wording can vary by model, control board and firmware.

How to read Burnham boiler error codes

Burnham (U.S. Boiler Company) condensing/combi boilers (Alpine, K2, Aspen) use the Sage (Sage2.1/2.2/2.3) boiler control, which reports a numbered Soft Lockout or Hard Lockout. A Soft Lockout makes the display turn red and the 'Help' button blink; the boiler restarts automatically once the condition clears. A Hard Lockout also turns the display red but requires a manual reset (Reset button on the 'Active Fault' display or on the Sage control) after the fault is corrected. On the LED/two-digit displays, soft codes appear after a flashing pattern and hard codes flash the letter 'E' followed by the number. The Sage soft/hard code set is the same across Alpine, K2 and Aspen; minor threshold differences exist between models (e.g. stack high-limit 204F on early Alpine vs 214F on K2/Aspen). The ESC is a SEPARATE product: it is an 85% AFUE chimney-vented CAST-IRON (non-condensing) gas boiler that uses the IQ Control System, NOT the Sage control. The ESC's IQ Boiler Control flashes 'Err' followed by a number for faults and 'StA' followed by a number for normal status states – a completely different code set, included separately below.

Burnham boiler acting up in Metro Vancouver? HeatLand’s licensed, TSBC-certified gas technicians diagnose and repair Burnham boilers across Greater Vancouver — including units we didn’t install.

Call (604) 330-3812Get a free repair estimateNo heat? Emergency repair

Burnham boiler error codes & what they mean

These are the Burnham boiler codes our Greater Vancouver technicians see most. Anything marked pro repair involves gas, electrical, sealed-combustion or control-board work that must be done by a licensed gas technician (TSBC-certified in BC) — never open gas or electrical components yourself.

CodeWhat it usually meansCommon causesSafe to check yourself
Soft Lockout 1Soft lockout: minimum time between starts has not been reached (normal anti-short-cycle delay used to avoid excessive cycling) pro repairnormal operation – the control is enforcing the minimum off-time between burner startsno action needed – this is a normal delay; the boiler will restart on its own; confirm the thermostat is calling for heat
Soft Lockout 2Soft lockout: Boiler Safety Limit / External Limit circuit open (terminals J6-1, 2 or 3 open) pro repairwater temperature above the external limit setting; external limit device defective or jumper not installed when no external device is used; optional low-water cutoff indicating low watercheck the system pressure gauge and top up via the filling loop per the user manual if low; confirm power and the thermostat call for heat; do not open the limit wiring; call a licensed technician if it recurs
Soft Lockout 3Soft lockout: Boiler Safety Limit open / Blocked Flue or Inlet switch open (ILK off; terminals J5-1 open) pro repairblocked or restricted flue or air-intake pipe; blocked vent causing the air pressure switch to open after the blower starts; loose wiring to the limit/switchcheck the outside vent/air-intake terminal for visible obstruction (snow, debris, nests) from a safe position; confirm power to the boiler; do not dismantle the flue or wiring; call a licensed technician if it recurs
Soft Lockout 7Soft lockout: shorted or open return temperature sensor pro repairshorted or mis-wired return sensor wiring; defective return sensora single reset may be attempted; this needs sensor diagnosis by a licensed technician
Soft Lockout 8Soft lockout: shorted or open supply temperature sensor pro repairshorted or mis-wired supply sensor wiring; defective supply sensora single reset may be attempted; this needs sensor diagnosis by a licensed technician
Soft Lockout 9Soft lockout: shorted or open Domestic Hot Water (DHW) temperature sensor pro repairshorted or mis-wired DHW sensor wiring; defective DHW sensora single reset may be attempted; this needs sensor diagnosis by a licensed technician
Soft Lockout 10Soft lockout: shorted or open flue gas (stack) temperature sensor pro repairshorted or mis-wired flue/stack temperature sensor wiring; defective flue/stack sensora single reset may be attempted; this needs sensor diagnosis by a licensed technician
Soft Lockout 11Soft lockout: ignition failure – flame failure after 5 tries to restart (flame rod not detecting flame) pro repairno gas, gas line not purged of air, or gas pressure below the rating-plate minimum; plugged condensate trap or plugged drain line in the trap; defective electrode, ignition cable or flame rodconfirm the gas supply is on and other gas appliances work; check the condensate drain/trap is not blocked or frozen; try a single reset (do not reset repeatedly)
Soft Lockout 13Soft lockout: flame rod shorted to ground pro repairshorted or mis-wired flame rod wiring; defective flame rod; plugged condensate trap or drain line in the trapcheck the condensate drain/trap is not blocked; a single reset may be attempted; this needs a licensed technician if it recurs
Soft Lockout 14Soft lockout: temperature rise between supply and return is too high (differential inlet/outlet high) pro repairinadequate boiler water flow (circulator not operating, or circulator/piping undersized); flow through the boiler reversed (incorrect piping or circulator orientation); air not purged from the systemcheck the system pressure gauge and top up if low per the user manual; ensure system/radiator isolation valves are open; if it recurs, call a licensed technician
Soft Lockout 15Soft lockout: control is reading a return sensor temperature higher than the supply sensor temperature (present at least ~75 seconds) pro repairno or insufficient boiler water flow (air not purged, valves closed); supply/return sensor wiring reversed; defective supply or return sensorcheck the system pressure gauge and top up if low per the user manual; ensure system/radiator valves are open; if it recurs, call a licensed technician
Soft Lockout 16Soft lockout: supply water temperature has risen too quickly pro repairinadequate boiler water flow; circulator not operating or circulator/piping undersizedcheck the system pressure gauge and top up if low per the user manual; ensure system/radiator valves are open; if it recurs, call a licensed technician
Soft Lockout 17Soft lockout (normal): waiting for blower/fan speed to match the purge and light-off setpoint pro repairnormal operation – the control is waiting for the blower to reach the correct purge/light-off speedno action needed – this is part of the normal start sequence; if the boiler never fires, call a licensed technician
Soft Lockout 27Soft lockout: undefined fault pro repairinternal control condition not otherwise defineda single reset may be attempted; if it recurs, a licensed technician should consult the factory
Soft Lockout 28Soft lockout: Air Proving Switch failed to close (also reported as 53) pro repairblocked vent or air intake, blocked or disconnected air-switch tube; blocked heat exchanger or burner; defective air proving switch or loose switch wiringcheck the outside vent/air-intake terminal for visible obstruction from a safe position; do not dismantle the flue or switch; call a licensed technician; a single reset may be attempted
Soft Lockout 53Soft lockout: Air Proving Switch failed to close (same condition as code 28) pro repairblocked vent or air intake, blocked or disconnected air-switch tube; blocked heat exchanger or burner; defective air proving switch or loose switch wiringcheck the outside vent/air-intake terminal for visible obstruction from a safe position; do not dismantle the flue or switch; call a licensed technician; a single reset may be attempted
Soft Lockout 54Soft lockout: Air Proving Switch failed to open (air switch closed when it should be open before the blower starts; leads to a manual-reset hard lockout) pro repairair proving switch jumpered; defective air proving switch; blower running before the start sequence (loss of communication between blower and control – defective harness, blower or control)no homeowner-safe internal action; a single reset may be attempted; this requires a licensed technician
Hard Lockout 4Hard lockout: Supply High Limit – control supply sensor detected temperatures in excess of 210F pro repairheating load far below the boiler's minimum firing rate; defective system circulator or no flow in the primary loop; defective boiler circulator or no/insufficient flow in the boiler loopcheck the system pressure gauge and top up if low per the user manual; ensure system/radiator valves are open so water can circulate; perform a single manual reset after the boiler cools; if it recurs, call a licensed technician
Hard Lockout 5Hard lockout: DHW high limit – control DHW sensor detected temperatures in excess of setpoint pro repairDHW sensor or wiring fault; DHW overheating conditionperform a single manual reset; if it recurs, call a licensed technician
Hard Lockout 6Hard lockout: Stack High Limit – control flue gas (stack) sensor detected temperatures over limit (about 204F on early Alpine; 214F / 101C on K2 and Aspen) pro repairheat exchanger needs to be cleaned; boiler over-fired; air-fuel mixture out of adjustmentperform a single manual reset after the boiler cools; this requires combustion service by a licensed technician if it recurs
Hard Lockout 12Hard lockout: flame detected out of sequence – a flame signal was present when there should be no flame pro repairdefective gas valve (verify inlet pressure is below the rating-plate maximum before replacing); plugged condensate trap or plugged drain line in the trapconfirm the gas supply is on and other gas appliances work; check the condensate drain/trap is not blocked; do not open the gas valve; this requires a licensed technician
Hard Lockout 18Hard lockout: Light-off rate proving failed – blower not running at light-off rate, or blower speed signal not detected by the control pro repairloose connection in the 120 VAC blower wiring; loose or mis-wired blower speed harness; defective blowerno homeowner-safe internal action; a single manual reset may be attempted; this requires a licensed technician
Hard Lockout 19Hard lockout: Purge rate proving failed – blower not running at purge rate, or blower speed signal not detected by the control pro repairloose connection in the 120 VAC blower wiring; loose or mis-wired blower speed harness; defective blowerno homeowner-safe internal action; a single manual reset may be attempted; this requires a licensed technician
Hard Lockout 20Hard lockout: invalid safety parameters – unacceptable control safety-related parameter detected pro repairsafety parameter verification required after a control change; internal control issueno homeowner-safe action; this requires a licensed technician (often a factory consult)
Hard Lockout 21Hard lockout: invalid modulation parameter – unacceptable control modulation-related parameter detected pro repaircontrol modulation parameter faulta single reset may be attempted; if it recurs, call a licensed technician
Hard Lockout 22Hard lockout: safety data verification needed – a safety-related parameter change was detected and verification has not been completed pro repaira safety-related control parameter was changed and verification was not performedno homeowner-safe action; this requires a licensed technician to verify parameters
Hard Lockout 23Hard lockout: 24VAC control power high or low pro repairloose connection or mis-wired 24VAC power harness; mis-wired harness causing a power-supply short to ground; defective transformer, or transformer frequency/voltage/VA not to specno homeowner-safe internal action; this requires a licensed technician
Hard Lockout 24Hard lockout: Fuel Valve Error – power detected at the fuel valve output when the fuel valve should be off pro repaircontrol or wiring fault at the fuel valve outputa single reset may be attempted; if it recurs, the control likely needs replacement by a licensed technician
Hard Lockout 25Hard lockout: Hardware Fault – internal control failure pro repairinternal Sage control hardware faulta single reset may be attempted; if it recurs, the control needs replacement by a licensed technician
Hard Lockout 26Hard lockout: Internal Fault – internal control failure pro repairinternal Sage control faulta single reset may be attempted; if it recurs, the control needs replacement by a licensed technician
Hard Lockout 27Hard lockout: undefined fault pro repairinternal control condition not otherwise defineda single reset may be attempted; if it recurs, the control may need replacement by a licensed technician
Hard Lockout 54Hard lockout: Air Proving Switch failed to open (manual-reset result of the air-switch-closed condition; see Soft Lockout 54) pro repairair proving switch jumpered or defective; blower running before the start sequence due to loss of communication with the controlno homeowner-safe internal action; a single manual reset may be attempted; this requires a licensed technician
Err 2ESC (IQ Control): Pressure Switch Failed to Open – while the blower is off the pressure switch contact is stuck closed pro repairkinked or blocked pressure switch tubing; defective pressure switch; wiring faultno homeowner-safe internal action; this requires a licensed technician
Err 4ESC (IQ Control): Flame Current Lower than Threshold pro repairpilot/flame sensing problem; dirty or misaligned pilot assemblyconfirm the gas supply is on and other gas appliances work; this requires a licensed technician
Err 6ESC (IQ Control): Flame Sensed Out of Normal Sequence (flame sensed before the gas valve opens or after it closes) pro repairgas valve not closing/operating correctly; flame-sensing faultconfirm the gas supply is on; do not open the gas valve; this requires a licensed technician
Err 18ESC (IQ Control): Electronics Failure pro repairinternal IQ control electronics fault; wiring faultcycle power to the control (single power reset); if it recurs, the control needs a licensed technician
Err 23ESC (IQ Control): Flame Sensed During Pre-Purge (flame sensed before the gas valve is signaled open) pro repairgas valve not closing/leaking by; flame-sensing faultconfirm the gas supply is on; do not open the gas valve; this requires a licensed technician
Err 29ESC (IQ Control): Pressure Switch Failed to Close – while the blower is on the pressure switch did not close pro repairblockage in the vent or air-intake system; tubing not connected / cracked / holding condensate; vent not installed per the manual or excessive wind (>40 mph) at a horizontal terminalcheck the outside vent/air-intake terminal for visible obstruction from a safe position; do not dismantle the vent or switch; this requires a licensed technician
Err 32ESC (IQ Control): Temperature Sensor Failure (open/short, high resistance, dual-sensor mismatch, or control hardware failure) pro repairtemperature sensor or interface failure; control hardware failurea single power reset may be attempted; this requires a licensed technician
Err 35ESC (IQ Control): Duplicate Zone Alarm pro repairzone configuration conflict (refer to the IQ Zone Panel instructions)no homeowner-safe action; this requires a licensed technician
Err 57ESC (IQ Control): Flame Rod Shorted to Burner Ground (can result from excessive flue-gas condensation) pro repairexcessive condensate / dry pilot; loose or damaged ignition wireno homeowner-safe internal action; this requires a licensed technician
Err 58ESC (IQ Control): AC Line Frequency Error – AC signal too noisy or frequency incorrect pro repairnoisy or out-of-spec mains supplyno homeowner-safe action; have the supply voltage checked by a licensed technician
Err 59ESC (IQ Control): Line Voltage Error – AC voltage out of specification (high or low) pro repairmains supply voltage too high or too lowconfirm the boiler breaker is on; no homeowner-safe internal action; this requires a licensed technician
Err 60ESC (IQ Control): Thermostat Input Higher than Threshold pro repairthermostat wiring faultno homeowner-safe internal action; this requires a licensed technician
Err 61ESC (IQ Control): Line Voltage Unstable (erratic supply voltage, possibly from heavy loads switching on and off) pro repairunstable mains supply voltageno homeowner-safe action; have the supply voltage checked by a licensed technician
Err 63ESC (IQ Control): Soft Lockout – Maximum Recycles Exceeded pro repairrepeated ignition recycles exceeded the allowed maximum (often a pilot/ignition issue)confirm the gas supply is on and other gas appliances work; a single reset may be attempted; if it recurs, this requires a licensed technician
Err 64ESC (IQ Control): Soft Lockout – Internal Failure (electronics detected an internal or wiring fault) pro repairactual controller internal fault or a wiring fault; pilot assembly problema single reset may be attempted; if it recurs, the control needs a licensed technician
Err 89ESC (IQ Control): Communication Lost pro repairwiring fault between the control and the IQ Zone Panel or IQ Reset Cardno homeowner-safe internal action; this requires a licensed technician

Burnham boiler codes we get called for most

Soft Lockout 11 — Soft lockout: ignition failure – flame failure after 5 tries to restart (flame rod not detecting flame)

Typical causes include no gas, gas line not purged of air, or gas pressure below the rating-plate minimum; plugged condensate trap or plugged drain line in the trap; defective electrode, ignition cable or flame rod. A few things are safe to check yourself (confirm the gas supply is on and other gas appliances work; check the condensate drain/trap is not blocked or frozen), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes Soft Lockout 11 on Burnham boilers throughout Greater Vancouver.

Err 2 — ESC (IQ Control): Pressure Switch Failed to Open – while the blower is off the pressure switch contact is stuck closed

Typical causes include kinked or blocked pressure switch tubing; defective pressure switch; wiring fault. A few things are safe to check yourself (no homeowner-safe internal action; this requires a licensed technician), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes Err 2 on Burnham boilers throughout Greater Vancouver.

Soft Lockout 14 — Soft lockout: temperature rise between supply and return is too high (differential inlet/outlet high)

Typical causes include inadequate boiler water flow (circulator not operating, or circulator/piping undersized); flow through the boiler reversed (incorrect piping or circulator orientation); air not purged from the system. A few things are safe to check yourself (check the system pressure gauge and top up if low per the user manual; ensure system/radiator isolation valves are open), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes Soft Lockout 14 on Burnham boilers throughout Greater Vancouver.

Soft Lockout 17 — Soft lockout (normal): waiting for blower/fan speed to match the purge and light-off setpoint

Typical causes include normal operation – the control is waiting for the blower to reach the correct purge/light-off speed. A few things are safe to check yourself (no action needed – this is part of the normal start sequence; if the boiler never fires, call a licensed technician), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes Soft Lockout 17 on Burnham boilers throughout Greater Vancouver.

Is it safe to keep running a Burnham boiler with a fault code?

Most Burnham fault codes put the boiler into a safe lockout for a reason. You can safely check the basics — gas supply on, power on, the thermostat calling for heat, system pressure in the normal range, and the condensate drain not frozen or blocked (a common cause in Vancouver cold snaps) — and restart it once. If the code returns, stop and book a technician. If you ever smell gas, leave the building and call your gas utility’s emergency line or 911 first. If a carbon-monoxide alarm sounds, get everyone out and call 911.

Burnham boiler repair across Greater Vancouver

HeatLand has kept Metro Vancouver homes comfortable since 1999. Our licensed, insured technicians diagnose and repair Burnham boilers — ignition faults, flame and sensor errors, low-pressure and pump problems, fan and flue faults, and control-board issues — including units we didn’t install. We’re brand-agnostic, carry common parts, and give you an honest repair-or-replace assessment with upfront pricing and a free estimate. If your boiler is beyond economical repair, we’ll show you right-sized, high-efficiency replacement options and the rebates available.

Need it sorted fast? We offer priority emergency boiler repair. Explore Boiler services, browse all boiler error codes by brand, or request a free estimate.

Burnham boiler service areas

We repair Burnham boilers across Greater Vancouver and the Fraser Valley, including:

VancouverBurnabySurreyRichmondCoquitlamNorth VancouverWest VancouverNew WestminsterLangleyDeltaPort CoquitlamPort MoodyMaple RidgeWhite RockAbbotsfordChilliwack

Burnham boiler error code FAQs

Can I reset my Burnham boiler myself?

Yes — power-cycling the reset button once is generally safe after you’ve checked the basics (gas supply on, power on, the thermostat calling for heat, system pressure in the normal range, and the condensate drain not frozen or blocked (a common cause in Vancouver cold snaps)). If the boiler faults again right away, stop and note the code — repeatedly resetting a boiler that keeps locking out can mask a real problem. Call a licensed, TSBC-certified gas technician to diagnose it.

What does the Burnham Soft Lockout 7 code mean?

On Burnham boilers, Soft Lockout 7 commonly indicates soft lockout: shorted or open return temperature sensor. Confirm the exact meaning against your unit’s manual — codes can vary by model and series — and have the repair done by a licensed, TSBC-certified gas technician. HeatLand fixes this across Greater Vancouver.

Do you repair Burnham boilers you didn’t install?

Yes. HeatLand is brand-agnostic and services Burnham boilers throughout Metro Vancouver and the Fraser Valley, whether or not we installed the unit. We carry common parts and give you an honest repair-or-replace assessment.

Is a Burnham boiler fault code an emergency?

No heat in cold weather is worth treating urgently. If you ever smell gas, leave the building and call your gas utility’s emergency line or 911 first. If a carbon-monoxide alarm sounds, get everyone out and call 911. For priority boiler repair across Greater Vancouver, call (604) 330-3812.

How much does Burnham boiler repair cost in Vancouver?

It depends on the fault. Many Burnham codes point to sensors, ignition or pump parts — usually far cheaper than replacement. We give upfront pricing and a free estimate before any work.

Burnham boiler acting up in Metro Vancouver? HeatLand’s licensed, TSBC-certified gas technicians diagnose and repair Burnham boilers across Greater Vancouver — including units we didn’t install.

Call (604) 330-3812Get a free repair estimateNo heat? Emergency repair

More Boiler error-code guides

HeatLand repairs every major boiler brand across Greater Vancouver. More brand guides:

Get your free estimate

Tell us what's going on and we'll get right back to you — no pressure, no obligation.

  • Free, no-obligation quotes
  • All major brands serviced
  • Metro Vancouver & the Fraser Valley
  • Financing & CleanBC rebate help
Prefer to talk now? Call (604) 330-3812

We'll only use your details to contact you about your request.