Goodman Air Conditioner Error Codes — Meanings, Causes & Repair in Greater Vancouver

Goodman Air Conditioner Error Codes — Meanings, Causes & Repair in Greater Vancouver

Seeing a fault code on your Goodman air conditioner? This guide explains what the most common Goodman air conditioner error codes mean, what’s safe to check yourself, and when to call HeatLand’s licensed HVAC technicians for Goodman air conditioner repair across Metro Vancouver and the Fraser Valley.

The codes below apply across common Goodman models (ComfortNet, standard). Meanings follow Goodman’s documented fault codes — always confirm against your unit’s own manual, because exact wording can vary by model, control board and firmware.

How to read Goodman air conditioner error codes

Standard single-stage Goodman ACs have NO on-unit fault display; the contactor simply energizes or not, and most diagnostics appear on the indoor air-handler/furnace control board. Communicating variable-speed inverter ACs (ComfortNet-compatible GVXC/GVZC family) show a 7-segment LED diagnostic code on the control board AND scroll a plain-language fault message on the ComfortNet / CTK04 communicating thermostat (Climate Talk message). Outdoor inverter faults use E-codes (e.g. E13, E24, E51); indoor air-handler faults use 2-character 7-segment codes (e.g. E5, b0, b9, d0). Stored faults are retrieved via the FAULT RECALL button on the board (last 6 faults) or the thermostat Equipment Status / Diagnostics screen.

Goodman air conditioner acting up in Metro Vancouver? HeatLand’s licensed HVAC technicians diagnose and repair Goodman air conditioners across Greater Vancouver — including units we didn’t install.

Call (604) 330-3812Get a free repair estimateNo heat? Emergency repair

Goodman air conditioner error codes & what they mean

These are the Goodman air conditioner codes our Greater Vancouver technicians see most. Anything marked pro repair involves electrical, refrigerant, sensor or control-board work that must be done by a licensed HVAC technician — never open the indoor/outdoor unit or refrigerant lines yourself.

CodeWhat it usually meansCommon causesSafe to check yourself
E5 (indoor board) / E_E5 BLOWN FUSEFuse open on the indoor air-handler control board (24V control fuse blown) pro repairBlown control-board fuse (F1U); Short in 24V control wiring; Open connector / loose low-voltage connectionConfirm the outdoor disconnect and indoor breaker are ON; Set the thermostat to Cool with a low setpoint; Try one single power cycle at the breaker
EE / no display (EMG mode) / INTERNAL FAULTInternal control fault or no power to the indoor blower control board pro repairNo 208/230V or 24V power to the blower/control board; Blown fuse or tripped circuit breaker; Short in 208/230V or 24V circuitCheck the indoor and outdoor breakers are ON; Confirm the furnace/air-handler power switch is ON; Try one single power cycle at the breaker
EF / E_EF AUXILIARY SWITCH OPENAuxiliary/safety switch open on the air handler (e.g. condensate float switch tripped) pro repairHigh water level in the evaporator drain pan (clogged condensate drain); Connected alarm device activated; Auxiliary alarm terminals openCheck for standing water near the indoor unit and a backed-up condensate drain; Set thermostat to Cool and retry after clearing any obvious drain blockage at the pan if safely accessible
b0 (Eb0) / NO ID AIRFLOW / Blower Motor Not RunningIndoor blower motor not running / estimated indoor airflow near 0 CFM pro repairFan/motor obstruction; Power interruption / low voltage; Incorrect or loose wiringCheck and replace a dirty air filter; Make sure supply and return vents are open and unblocked; Try one single power cycle at the breaker
b1 (E_b1) / Blower Communication ErrorCommunication error between the control board and the blower motor pro repairIncorrect or loose wiring; Power interruption / low voltage; Faulty control board or motorTry one single power cycle at the breaker
b9 (Eb9) / LOW ID AIRFLOWEstimated indoor airflow is lower than the airflow requirement (low indoor airflow, minor code) pro repairToo much static pressure (restricted ductwork/filter); Failed indoor blower motor; Blower motor not properly connectedReplace a dirty air filter; Open all supply and return vents and clear any blockage; Make sure the return grille is not obstructed
d0 (E_d0) / NO NET DATA / Ed0Control board does not have the shared data it needs on the network to operate pro repairNo shared data loaded on the network; Communicating system not yet commissionedNo homeowner fix; requires technician data programming
d1 (E_d1) / INVALID DATA / Ed1Invalid shared data on the network for the control module pro repairWrong shared data on the network; Network data invalid for the control moduleNo homeowner fix; requires technician data programming
E13High pressure (critical) – equipment experiencing frequent high-pressure faults pro repairBlocked/restricted condenser coil or lines; Service (stop) valve not fully open; Refrigerant overchargeClear leaves, grass and debris from around the outdoor condenser and keep it free of obstructions; Set thermostat to Cool and try one single power cycle at the breaker
E15Low pressure (critical) – equipment experiencing frequent low-pressure faults pro repairService (stop) valve not fully open; Restriction in refrigerant lines; Low refrigerant charge / refrigerant leakReplace a dirty air filter and make sure indoor airflow is not blocked; Set thermostat to Cool and retry once
E17Compressor fail – equipment experiencing frequent compressor faults pro repairService (stop) valve not fully open; Compressor wire lost phase / wiring issue; Compressor motor failureTry one single power cycle at the breaker
E19PCB or fan fail – frequent outdoor control board and/or fan motor faults pro repairObstruction in fan rotation; Outdoor fan motor not properly connected; Outdoor fan not runningCheck the outdoor fan grille for debris (leaves/branches) and clear obstructions; Try one single power cycle at the breaker
E22High discharge temperature – frequent high discharge-temperature faults; discharge thermistor may be misplaced pro repairDischarge thermistor inoperable or improperly connected/positioned; Low refrigerant charge or overcharge; Faulty compressorMake sure the outdoor condenser is clear of debris; Try one single power cycle at the breaker
E23Discharge temperature sensor fail – discharge temperature sensor out of range pro repairDischarge thermistor inoperable or improperly connectedNo homeowner fix; requires technician sensor service
E24HPS open – the high-pressure switch is open pro repairHigh-pressure switch inoperable; Condition that caused high pressure (dirty coil, blocked condenser, overcharge)Clear debris from around the outdoor condenser; Try one single power cycle at the breaker
E25 / AIR SENSOR FLTOutdoor air temperature sensor is open or shorted pro repairFaulty outdoor thermistor sensor or disconnected sensorNo homeowner fix; requires technician sensor service
E26 / PRESSURE SENSORPressure sensor not reacting properly pro repairLow-pressure sensor inoperable or not properly connectedNo homeowner fix; requires technician service
E31 / HI LEAK CURRENTControl detected high leakage current (high-voltage leakage to ground) pro repairImproper ground; Faulty compressorTurn the unit off and leave it off; this is an electrical fault – call a licensed technician
E34 / CURRENT SPIKEHigh current condition detected, indicating potential for a short circuit pro repairCurrent spike in supply; Service (stop) valve not fully open; Compressor wire lost phaseLeave the unit off; this is an electrical fault – call a licensed technician
E35 / HIGH CURRENTHigh current condition detected on the outdoor control board pro repairShort-circuit condition; Service (stop) valve not fully open; Refrigerant overchargeLeave the unit off; this is an electrical fault – call a licensed technician
E41 / LOW REFRIGERANTControl detected a low refrigerant condition pro repairRefrigerant leak; Low refrigerant charge; Thermistors inoperable or not properly connectedNo homeowner fix; refrigerant work must be done by a licensed technician
E42 / LOW LINE VOLTControl detected a low power-supply voltage condition pro repairLow line voltage supply; Tripped breaker / blown fuse; Utility supply issueCheck the breaker for the AC is fully ON (not tripped); Try one single power cycle at the breaker
E43 / HIGH LINE VOLTControl detected a high power-supply voltage condition pro repairHigh line voltage supply; Utility supply issueNo homeowner fix; line-voltage issue requires a technician/utility
E44 / OP TEMP RANGEOutdoor temperature is outside the recommended operating range; unit may still operate normally DIY-checkableAmbient air temperature too high or too low for normal operationWait and retry during a more moderate outdoor temperature; Try one single power cycle at the breaker
E50 / LINE VOLT CTRLVoltage issue on the outdoor control board pro repairHigh or low voltage from supply; Faulty control boardCheck the breaker is fully ON; Try one single power cycle at the breaker
E51 / OD COMM ERRORCommunication issue detected by the outdoor control board (communicating/ComfortNet system) pro repairCommunication wiring disconnected or looseTry one single power cycle at the breaker
E11 / RUN SYS TESTThermostat message indicating the required start-up System Verification Test must be run (commissioning step, not a failure) pro repairInitial system test not yet completed after install or board/data changeNo action needed by homeowner; the installer runs the System Verification Test from the ComfortNet menu
Ed0 / D1 INVALID DATA / D2 INVALID SYSTEM / D3 INVALID CONFIG / D4 INVALID MC DATA (outdoor)Outdoor control board shared-data / configuration faults (no data, invalid data, airflow mismatch, hardware mismatch, or rejected data loader data) pro repairOutdoor unit shared data missing, invalid, or incompatible with the system; Communication wiring loose; Data loader (BTSDL01) data rejected or wrongNo homeowner fix; requires technician data programming

Goodman air conditioner codes we get called for most

E5 (indoor board) / E_E5 BLOWN FUSE — Fuse open on the indoor air-handler control board (24V control fuse blown)

Typical causes include blown control-board fuse (f1u); short in 24v control wiring; open connector / loose low-voltage connection. A few things are safe to check yourself (Confirm the outdoor disconnect and indoor breaker are ON; Set the thermostat to Cool with a low setpoint), but the repair is a licensed HVAC technician job. HeatLand diagnoses and fixes E5 (indoor board) / E_E5 BLOWN FUSE on Goodman air conditioners throughout Greater Vancouver.

E22 — High discharge temperature – frequent high discharge-temperature faults; discharge thermistor may be misplaced

Typical causes include discharge thermistor inoperable or improperly connected/positioned; low refrigerant charge or overcharge; faulty compressor. A few things are safe to check yourself (Make sure the outdoor condenser is clear of debris; Try one single power cycle at the breaker), but the repair is a licensed HVAC technician job. HeatLand diagnoses and fixes E22 on Goodman air conditioners throughout Greater Vancouver.

d1 (E_d1) / INVALID DATA / Ed1 — Invalid shared data on the network for the control module

Typical causes include wrong shared data on the network; network data invalid for the control module. A few things are safe to check yourself (No homeowner fix; requires technician data programming), but the repair is a licensed HVAC technician job. HeatLand diagnoses and fixes d1 (E_d1) / INVALID DATA / Ed1 on Goodman air conditioners throughout Greater Vancouver.

E13 — High pressure (critical) – equipment experiencing frequent high-pressure faults

Typical causes include blocked/restricted condenser coil or lines; service (stop) valve not fully open; refrigerant overcharge. A few things are safe to check yourself (Clear leaves, grass and debris from around the outdoor condenser and keep it free of obstructions; Set thermostat to Cool and try one single power cycle at the breaker), but the repair is a licensed HVAC technician job. HeatLand diagnoses and fixes E13 on Goodman air conditioners throughout Greater Vancouver.

Is it safe to keep running a Goodman air conditioner with a fault code?

Most Goodman fault codes put the air conditioner into a safe lockout for a reason. You can safely check the basics — the power and breaker on, the air filter clean, the outdoor condenser clear of debris, and the thermostat set to cool — and restart it once. If the code returns, stop and book a technician. Air-conditioner faults are electrical and refrigerant issues — never open the unit or touch the wiring or refrigerant lines yourself.

Goodman air conditioner repair across Greater Vancouver

HeatLand has kept Metro Vancouver homes comfortable since 1999. Our licensed, insured technicians diagnose and repair Goodman air conditioners — sensor and thermistor errors, communication faults, fan and compressor problems, refrigerant and pressure faults, and control-board issues — including units we didn’t install. We’re brand-agnostic, carry common parts, and give you an honest repair-or-replace assessment with upfront pricing and a free estimate. If your air conditioner is beyond economical repair, we’ll show you right-sized, high-efficiency replacement options and the rebates available.

Need it sorted fast? We offer priority emergency air conditioner repair. Explore Air Conditioner services, browse all air conditioner error codes by brand, or request a free estimate.

Goodman air conditioner service areas

We repair Goodman air conditioners across Greater Vancouver and the Fraser Valley, including:

VancouverBurnabySurreyRichmondCoquitlamNorth VancouverWest VancouverNew WestminsterLangleyDeltaPort CoquitlamPort MoodyMaple RidgeWhite RockAbbotsfordChilliwack

Goodman air conditioner error code FAQs

Can I reset my Goodman air conditioner myself?

Yes — power-cycling the unit at the breaker once is generally safe after you’ve checked the basics (the power and breaker on, the air filter clean, the outdoor condenser clear of debris, and the thermostat set to cool). If the air conditioner faults again right away, stop and note the code — repeatedly resetting a air conditioner that keeps locking out can mask a real problem. Call a licensed HVAC technician to diagnose it.

What does the Goodman b1 (E_b1) / Blower Communication Error code mean?

On Goodman air conditioners, b1 (E_b1) / Blower Communication Error commonly indicates communication error between the control board and the blower motor. Confirm the exact meaning against your unit’s manual — codes can vary by model and series — and have the repair done by a licensed HVAC technician. HeatLand fixes this across Greater Vancouver.

Do you repair Goodman air conditioners you didn’t install?

Yes. HeatLand is brand-agnostic and services Goodman air conditioners throughout Metro Vancouver and the Fraser Valley, whether or not we installed the unit. We carry common parts and give you an honest repair-or-replace assessment.

Is a Goodman air conditioner fault code an emergency?

No heat in cold weather or no cooling in a heat wave is worth treating urgently. For priority air conditioner repair across Greater Vancouver, call (604) 330-3812.

How much does Goodman air conditioner repair cost in Vancouver?

It depends on the fault. Many Goodman codes point to sensors, thermistors, capacitors or control parts — usually far cheaper than replacement. We give upfront pricing and a free estimate before any work.

Goodman air conditioner acting up in Metro Vancouver? HeatLand’s licensed HVAC technicians diagnose and repair Goodman air conditioners across Greater Vancouver — including units we didn’t install.

Call (604) 330-3812Get a free repair estimateNo heat? Emergency repair

More Air Conditioner error-code guides

HeatLand repairs every major air conditioner brand across Greater Vancouver. More brand guides:

Get your free estimate

Tell us what's going on and we'll get right back to you — no pressure, no obligation.

  • Free, no-obligation quotes
  • All major brands serviced
  • Metro Vancouver & the Fraser Valley
  • Financing & CleanBC rebate help
Prefer to talk now? Call (604) 330-3812

We'll only use your details to contact you about your request.