Daikin Air Conditioner Error Codes — Meanings, Causes & Repair in Greater Vancouver

Daikin Air Conditioner Error Codes — Meanings, Causes & Repair in Greater Vancouver

Seeing a fault code on your Daikin air conditioner? This guide explains what the most common Daikin air conditioner error codes mean, what’s safe to check yourself, and when to call HeatLand’s licensed HVAC technicians for Daikin air conditioner repair across Metro Vancouver and the Fraser Valley.

The codes below apply across common Daikin models (FIT, DX series). Meanings follow Daikin’s documented fault codes — always confirm against your unit’s own manual, because exact wording can vary by model, control board and firmware.

How to read Daikin air conditioner error codes

On Daikin FIT and communicating inverter ducted systems sold in North America (which share the Goodman/ClimateTalk inverter platform), the outdoor control board displays a numeric fault code. On the outdoor PCB 7-segment display this appears as an 'E' followed by the number (for example fault 24 shows as 'E24'); the same number is reported by name on the Daikin communicating thermostat. These codes come from the official Daikin ClimateTalk unitary 'AC & HP' (outdoor unit / condenser) fault table.

Daikin air conditioner acting up in Metro Vancouver? HeatLand’s licensed HVAC technicians diagnose and repair Daikin air conditioners across Greater Vancouver — including units we didn’t install.

Call (604) 330-3812Get a free repair estimateNo heat? Emergency repair

Daikin air conditioner error codes & what they mean

These are the Daikin air conditioner codes our Greater Vancouver technicians see most. Anything marked pro repair involves electrical, refrigerant, sensor or control-board work that must be done by a licensed HVAC technician — never open the indoor/outdoor unit or refrigerant lines yourself.

CodeWhat it usually meansCommon causesSafe to check yourself
11System Test required for start up (SYSTEM TEST incomplete or currently running). This is a message-only status, not a hardware fault pro repairIncomplete SYSTEM TEST after installation; SYSTEM TEST is currently runningThis is an installation/commissioning message; if the system is newly installed or was just serviced, allow the technician to complete the system test
12General memory error on the outdoor control board pro repairHigh electrical noise; Faulty control boardTurn the thermostat to off, then try a single power reset at the outdoor disconnect or breaker
13Experiencing frequent high pressure faults (critical lockout) pro repairBlocked or restricted condenser coil and/or lines; Stop (service) valve not completely open; Overcharged refrigerantMake sure the outdoor condenser is clear of leaves, grass clippings, dirt, and obstructions blocking airflow; Check and replace a dirty air filter; Confirm nothing is restricting airflow around the outdoor unit
14Experiencing frequent high pressure faults but acceptable to run (minor) pro repairBlocked or restricted condenser coil and/or lines; Stop (service) valve not completely open; Overcharged refrigerantClear leaves, debris, and vegetation away from the outdoor condenser coil; Check and replace a dirty air filter
15Frequent low pressure faults (critical lockout) pro repairStop (service) valve not completely open; Restriction in refrigerant lines; Low refrigerant chargeCheck and replace a dirty air filter; Make sure supply and return vents are open and unobstructed
16Frequent low pressure faults (minor) pro repairStop (service) valve not completely open; Restriction in refrigerant lines; Low refrigerant chargeCheck and replace a dirty air filter; Make sure supply and return vents are open and unobstructed
17Frequent compressor faults pro repairStop (service) valve not completely open; Compressor wire has lost phase; Compressor motor failureConfirm the outdoor disconnect and breaker are on; Try a single power reset, then call a licensed technician if the code returns
18Outdoor control board error pro repairOutdoor fan motor not connected properly; Faulty control board; Electrical noiseTry a single power reset at the outdoor disconnect or breaker, then call a licensed technician if the code returns
19Outdoor unit PCB or fan failure error pro repairObstruction in fan rotation; Outdoor fan motor not connected properly; Outdoor fan not runningCheck the outdoor fan grille and clear any debris that could block the fan (with the power off at the disconnect); Confirm the outdoor breaker and disconnect are on
20EEV coil is not connected (outdoor electronic expansion valve coil not connected) pro repairOutdoor EEV coil is not connected; Faulty outdoor EEV coilNo safe homeowner check; this requires a technician to inspect the EEV coil wiring
21Experiencing frequent low discharge superheat faults pro repairThermistors inoperable or improperly connected; Faulty indoor or outdoor EEV/EEV coil; Faulty indoor TXVNo safe homeowner check; this is an internal refrigerant-control fault for a technician
22High discharge temperature error pro repairDischarge thermistor inoperable or improperly connected; Discharge thermistor in incorrect position or off; Low refrigerant chargeClear debris and vegetation from the outdoor condenser to improve airflow; Check and replace a dirty air filter
23Discharge temperature sensor failure pro repairDischarge thermistor inoperable or improperly connectedNo safe homeowner check; the sensor and its wiring must be tested by a technician
24High pressure switch is open pro repairHigh pressure switch (HPS) inoperable; High system pressure from restricted airflow, dirty condenser, overcharge, or stop valve not fully openMake sure the outdoor condenser coil is clear of leaves, dirt, and obstructions; Check and replace a dirty air filter; Try a single power reset, then call a licensed technician if the code returns
25Outdoor temperature sensor error pro repairFaulty or disconnected outdoor thermistor sensorNo safe homeowner check; the sensor must be inspected and tested by a technician
26Pressure sensor not reacting properly pro repairLow pressure sensor inoperable or not properly connectedNo safe homeowner check; the pressure sensor and wiring must be checked by a technician
28Outdoor coil temperature sensor error pro repairOutdoor coil thermistor inoperable or not properly connectedNo safe homeowner check; the sensor connection must be inspected by a technician
29Liquid temperature sensor error pro repairLiquid thermistor inoperable or not properly connectedNo safe homeowner check; the sensor connection must be inspected by a technician
30Control board may need to be replaced (communication/wiring fault to the control board) pro repairWiring to control board disconnected; Faulty control board; Electrical noiseTry a single power reset at the outdoor disconnect or breaker, then call a licensed technician if the code returns
31High current leak pro repairImproper ground; Faulty compressorNo safe homeowner check; this is an electrical-safety fault that must be diagnosed by a licensed technician
32Outdoor unit control board high temperature fault (critical) pro repairAmbient air conditions too high; Cooling bracket screws missing or loose (2-4 ton); Poor or missing thermal grease on control board cooling bracket (2-4 ton)Make sure the outdoor unit has clearance and is not surrounded by obstructions that trap heat; Clear debris from around the condenser; Try a single power reset during cooler ambient conditions
33Outdoor unit control board high temperature fault but acceptable to run (minor) pro repairAmbient air conditions too high; Cooling bracket screws missing or loose (2-4 ton); Poor or missing thermal grease on control board cooling bracket (2-4 ton)Make sure the outdoor unit has clearance and is not surrounded by obstructions that trap heat; Clear debris from around the condenser
34Outdoor unit PCB detected a possible short circuit (current spike) pro repairCurrent spike in supply; Stop valve not completely open; Compressor wire has lost phaseTry a single power reset at the outdoor disconnect or breaker, then call a licensed technician if the code returns
35Outdoor unit PCB detected a high current condition pro repairShort circuit condition; Stop valve not completely open; Overcharged refrigerantConfirm the outdoor unit has proper installation clearances and is not blocked; Try a single power reset, then call a licensed technician if the code returns
36Startup procedure error pro repairBlocked or restricted condenser coil and/or lines; Compressor wire has lost phase; Inconsistent compressor loadClear debris and vegetation from the outdoor condenser coil; Check and replace a dirty air filter
37Control board error (outdoor) pro repairOutdoor fan motor not connected properly; Faulty control boardTry a single power reset at the outdoor disconnect or breaker, then call a licensed technician if the code returns
38Compressor voltage error pro repairHigh or low voltage from supply; Compressor wire has lost phase; Faulty control boardCheck whether other large appliances or the home are experiencing power/voltage issues; if so, contact the utility; Try a single power reset
41Low refrigerant condition error pro repairRefrigerant leak; Low refrigerant charge; Thermistors inoperable or not properly connectedNo safe homeowner check; refrigerant must only be handled by a licensed technician
42Low power supply voltage condition detected pro repairLow line voltage supplyCheck the circuit breaker and outdoor disconnect are fully on; If other lights/appliances are dimming or the whole home has low voltage, contact the utility
43High power supply voltage condition detected pro repairHigh line voltage supplyIf a high-voltage condition is suspected across the home, contact the utility; do not open any electrical panels yourself
44Recommended outdoor operational temperature is out of range (minor) DIY-checkableAmbient air conditions too high or too low for the unit's operating rangeThis is usually a normal extreme-weather condition; cycle power and retry when outdoor temperatures are within the usable range
50Voltage issue on the control board (see manual for troubleshooting info) pro repairHigh or low voltage from supply; Faulty control boardConfirm the breaker and disconnect are fully on; if a home-wide voltage problem is suspected, contact the utility; Try a single power reset
51Potential communication issues detected by the outdoor control board pro repairCommunication wiring disconnectedTry a single power reset at the outdoor disconnect or breaker, then call a licensed technician if the code returns
52Experiencing frequent compressor faults but acceptable to run (minor) pro repairStop valve not completely open; Compressor wire has lost phase; Compressor motor failureConfirm the outdoor disconnect and breaker are on; Try a single power reset, then call a licensed technician if the code persists
56Suction temperature sensor failure pro repairSuction thermistor inoperable or not properly connected; Obstruction inside ductworkCheck and replace a dirty air filter and make sure vents are open; Sensor wiring itself must be checked by a technician

Daikin air conditioner codes we get called for most

12 — General memory error on the outdoor control board

Typical causes include high electrical noise; faulty control board. A few things are safe to check yourself (Turn the thermostat to off, then try a single power reset at the outdoor disconnect or breaker), but the repair is a licensed HVAC technician job. HeatLand diagnoses and fixes 12 on Daikin air conditioners throughout Greater Vancouver.

23 — Discharge temperature sensor failure

Typical causes include discharge thermistor inoperable or improperly connected. A few things are safe to check yourself (No safe homeowner check; the sensor and its wiring must be tested by a technician), but the repair is a licensed HVAC technician job. HeatLand diagnoses and fixes 23 on Daikin air conditioners throughout Greater Vancouver.

17 — Frequent compressor faults

Typical causes include stop (service) valve not completely open; compressor wire has lost phase; compressor motor failure. A few things are safe to check yourself (Confirm the outdoor disconnect and breaker are on; Try a single power reset, then call a licensed technician if the code returns), but the repair is a licensed HVAC technician job. HeatLand diagnoses and fixes 17 on Daikin air conditioners throughout Greater Vancouver.

13 — Experiencing frequent high pressure faults (critical lockout)

Typical causes include blocked or restricted condenser coil and/or lines; stop (service) valve not completely open; overcharged refrigerant. A few things are safe to check yourself (Make sure the outdoor condenser is clear of leaves, grass clippings, dirt, and obstructions blocking airflow; Check and replace a dirty air filter), but the repair is a licensed HVAC technician job. HeatLand diagnoses and fixes 13 on Daikin air conditioners throughout Greater Vancouver.

Is it safe to keep running a Daikin air conditioner with a fault code?

Most Daikin fault codes put the air conditioner into a safe lockout for a reason. You can safely check the basics — the power and breaker on, the air filter clean, the outdoor condenser clear of debris, and the thermostat set to cool — and restart it once. If the code returns, stop and book a technician. Air-conditioner faults are electrical and refrigerant issues — never open the unit or touch the wiring or refrigerant lines yourself.

Daikin air conditioner repair across Greater Vancouver

HeatLand has kept Metro Vancouver homes comfortable since 1999. Our licensed, insured technicians diagnose and repair Daikin air conditioners — sensor and thermistor errors, communication faults, fan and compressor problems, refrigerant and pressure faults, and control-board issues — including units we didn’t install. We’re brand-agnostic, carry common parts, and give you an honest repair-or-replace assessment with upfront pricing and a free estimate. If your air conditioner is beyond economical repair, we’ll show you right-sized, high-efficiency replacement options and the rebates available.

Need it sorted fast? We offer priority emergency air conditioner repair. Explore Air Conditioner services, browse all air conditioner error codes by brand, or request a free estimate.

Daikin air conditioner service areas

We repair Daikin air conditioners across Greater Vancouver and the Fraser Valley, including:

VancouverBurnabySurreyRichmondCoquitlamNorth VancouverWest VancouverNew WestminsterLangleyDeltaPort CoquitlamPort MoodyMaple RidgeWhite RockAbbotsfordChilliwack

Daikin air conditioner error code FAQs

Can I reset my Daikin air conditioner myself?

Yes — power-cycling the unit at the breaker once is generally safe after you’ve checked the basics (the power and breaker on, the air filter clean, the outdoor condenser clear of debris, and the thermostat set to cool). If the air conditioner faults again right away, stop and note the code — repeatedly resetting a air conditioner that keeps locking out can mask a real problem. Call a licensed HVAC technician to diagnose it.

What does the Daikin 17 code mean?

On Daikin air conditioners, 17 commonly indicates frequent compressor faults. Confirm the exact meaning against your unit’s manual — codes can vary by model and series — and have the repair done by a licensed HVAC technician. HeatLand fixes this across Greater Vancouver.

Do you repair Daikin air conditioners you didn’t install?

Yes. HeatLand is brand-agnostic and services Daikin air conditioners throughout Metro Vancouver and the Fraser Valley, whether or not we installed the unit. We carry common parts and give you an honest repair-or-replace assessment.

Is a Daikin air conditioner fault code an emergency?

No heat in cold weather or no cooling in a heat wave is worth treating urgently. For priority air conditioner repair across Greater Vancouver, call (604) 330-3812.

How much does Daikin air conditioner repair cost in Vancouver?

It depends on the fault. Many Daikin codes point to sensors, thermistors, capacitors or control parts — usually far cheaper than replacement. We give upfront pricing and a free estimate before any work.

Daikin air conditioner acting up in Metro Vancouver? HeatLand’s licensed HVAC technicians diagnose and repair Daikin air conditioners across Greater Vancouver — including units we didn’t install.

Call (604) 330-3812Get a free repair estimateNo heat? Emergency repair

More Air Conditioner error-code guides

HeatLand repairs every major air conditioner brand across Greater Vancouver. More brand guides:

Get your free estimate

Tell us what's going on and we'll get right back to you — no pressure, no obligation.

  • Free, no-obligation quotes
  • All major brands serviced
  • Metro Vancouver & the Fraser Valley
  • Financing & CleanBC rebate help
Prefer to talk now? Call (604) 330-3812

We'll only use your details to contact you about your request.