Seeing a fault code on your Baxi boiler? This guide explains what the most common Baxi boiler error codes mean, what’s safe to check yourself, and when to call HeatLand’s licensed, TSBC-certified gas technicians for Baxi boiler repair across Metro Vancouver and the Fraser Valley.
The codes below apply across common Baxi models (Luna, Duo-tec, Nuvola). Meanings follow Baxi’s documented fault codes — always confirm against your unit’s own manual, because exact wording can vary by model, control board and firmware.
How to read Baxi boiler error codes
Baxi displays a fault as an 'E' prefix followed by a number (e.g. E110, E133, E160). On the boiler controller the number appears with a wrench/service icon; resettable faults can be cleared by turning the selector to the Reset position for at least 5 seconds. Baxi's North American service documentation lists the codes as bare numbers (e.g. '110'), which correspond to the E-codes shown on the display. Active codes vary by model and software version.
Baxi boiler acting up in Metro Vancouver? HeatLand’s licensed, TSBC-certified gas technicians diagnose and repair Baxi boilers across Greater Vancouver — including units we didn’t install.
Call (604) 330-3812Get a free repair estimateNo heat? Emergency repairBaxi boiler error codes & what they mean
These are the Baxi boiler codes our Greater Vancouver technicians see most. Anything marked pro repair involves gas, electrical, sealed-combustion or control-board work that must be done by a licensed gas technician (TSBC-certified in BC) — never open gas or electrical components yourself.
| Code | What it usually means | Common causes | Safe to check yourself |
|---|---|---|---|
| E09 | Gas valve connection fault (wiring/connection between the gas valve and the PCB) pro repair | loose or disconnected gas valve wiring connector; damaged wiring harness to the gas valve; faulty PCB | confirm power to the boiler is on; do not open the gas valve or any wiring; this requires a licensed technician; try a single reset if the code is resettable |
| E10 | Outdoor temperature sensor fault (open or short circuit) pro repair | faulty outdoor sensor; break or short in the outdoor sensor wiring; faulty PCB | if an outdoor sensor is fitted, no homeowner-safe action – call a licensed technician; try a single reset if the code is resettable |
| E15 | Gas valve command fault (electronic control of the gas valve) pro repair | faulty gas valve wiring harness; faulty gas valve; faulty PCB | do not attempt gas-side checks; call a licensed technician; try a single reset if the code is resettable |
| E20 | Central heating (flow/supply) NTC temperature sensor fault pro repair | faulty CH NTC sensor (out of calibration); loose or broken sensor wiring; faulty PCB | press reset once if the code is resettable; if it recurs, call a licensed technician |
| E28 | Flue / heat exchanger NTC (flue high-limit) sensor fault pro repair | loose connection at the flue high limit and control board; short in the wiring harness; faulty flue sensor | press reset once if the code is resettable; if it recurs, call a licensed technician |
| E40 | Return NTC temperature sensor fault pro repair | faulty return NTC sensor (out of calibration); loose or broken sensor wiring; faulty PCB | press reset once if the code is resettable; if it recurs, call a licensed technician |
| E50 | Domestic hot water (DHW) NTC supply sensor fault pro repair | faulty DHW NTC sensor (out of calibration); loose or broken sensor wiring; faulty PCB | press reset once if the code is resettable; if it recurs, call a licensed technician |
| E53 | Obstruction in the flue pipe / flue blockage pro repair | blocked or obstructed flue/vent; vent not sloped back toward the boiler (dips trapping condensate); pinched gasket on the inner (exhaust) pipe of a concentric vent | check the outside flue terminal for visible obstruction (snow, debris, nests) from a safe position; do not open or dismantle the flue; call a licensed technician; try a single reset if the code is resettable |
| E55 | PCB not programmed (electronic board not configured / parameter data not loaded) pro repair | memory stick not connected properly to the PCB after a board replacement; incomplete PCB programming during service | no homeowner-safe action; this occurs after a board replacement and needs a licensed technician |
| E83 | Communication problem between the boiler PCB and the control unit / room unit (eBUS/M2 bus). Also reported as E84, E85, E86, E87 pro repair | wiring fault between the modulating room unit and the M2 bus terminals; short circuit in the bus wiring; faulty control unit or PCB | check the room control/thermostat batteries if applicable; restore power at the isolator and allow communication to re-establish; if it recurs, call a licensed technician |
| E109 | Pre-circulation alarm (temporary fault) – insufficient water circulation detected before firing pro repair | pump not running / seized or sticking; restriction or blockage in the boiler or system; air not fully purged from the system | read the pressure gauge and top up via the filling loop per the user manual if low; ensure system/radiator isolation valves are open; try a single reset if the code is resettable |
| E110 | Safety thermostat (high-limit) tripped due to over-temperature of the primary water pro repair | poor circulation (seized pump or impeller not spinning); restrictions/blockage in the system; air trapped in the system | check the system pressure gauge is in the normal range; ensure radiator/system valves are open so water can circulate; turn the selector to Reset for at least 5 seconds (single reset) |
| E118 | Hydraulic (system water) pressure too low pro repair | low system pressure / water loss from a leak; air in the system or closed shutoff valve; expansion tank not correctly pressurized | read the pressure gauge; if low, top up via the filling loop per the user manual (typical target around 12-15 psi / ~1 bar cold); look for visible leaks around the boiler, pipework and radiators; ensure shutoff valves are open |
| E119 | Water pressure switch not operated (primary water pressure below ~0.5 bar / low-pressure switch open) pro repair | low system pressure / water loss; faulty water pressure switch; air-lock or closed valve | read the pressure gauge; if low, top up via the filling loop per the user manual; look for visible leaks; try a single reset after re-pressurising |
| E125 | Circulation fault (primary circuit) – no circulation of water detected pro repair | pump not running or seized; restriction/blockage in the system; wiring to the pump disconnected or broken | check the pressure gauge and top up if low per the user manual; ensure system/radiator valves are open; try a single reset; if E125 recurs, call a licensed technician |
| E128 | Loss of flame during operation (flame detected then lost while running) pro repair | flame sensor gap incorrect, dirty or damaged; loose flame-sensor wiring or broken wire; incorrect polarity / poor grounding | confirm the gas supply is on and other gas appliances work; try a single reset (do not reset repeatedly); if it recurs, call a licensed technician |
| E130 | Flue NTC sensor tripped due to over-temperature (flue gases too hot) pro repair | seized pump / poor circulation causing high temperature; blocked or restricted heat exchanger; pinched vent gasket or vent not sloped/supported (dips) | check the system pressure gauge is in the normal range; check the outside flue terminal for visible obstruction from a safe position; turn the selector to Reset for at least 5 seconds (single reset) |
| E131 | Thermal fuse (thermo-fuse) tripped due to over-temperature pro repair | over-temperature event at the primary heat exchanger; faulty/blown thermal fuse; damaged or fouled primary heat exchanger | check the system pressure gauge reading; no homeowner-safe internal action; call a licensed technician; try a single reset if the code is resettable |
| E133 | Ignition failure – no spark, no flame, or no flame signal (also covers interruption of gas supply / flame failure) pro repair | gas supply off, gas line not purged of air, or low gas pressure; faulty spark/ignition electrode or wiring; incorrect electrode spacing | confirm the gas supply is on and other gas appliances work; check the condensate drain is not blocked or frozen; turn the selector to Reset for at least 5 seconds (single reset, no more than 2-3 attempts) |
| E134 | Gas supply valve blocked / elapsed time with gas valve open but no gas pro repair | gas valve fault; gas supply interruption; faulty PCB | confirm the gas supply is on and other gas appliances work; do not attempt gas-side checks; call a licensed technician; try a single reset if the code is resettable |
| E135 | Internal (electronics) error pro repair | polarity/grounding issue or boiler not on a dedicated circuit; water or water residue on the PCB; faulty PCB | restore power at the isolator and try a single reset; if it recurs, call a licensed technician |
| E160 | Fan fault (fan not running at the correct speed or no fan feedback) pro repair | loose fan wiring at the fan or PCB connectors; seized or sticking fan; no supply voltage to the fan | try a single reset if the code is resettable; no internal access; call a licensed technician if it recurs |
| E162 | Incorrect power supply frequency (mains Hz mismatch). Also reported as E317 pro repair | boiler parameter set for the wrong mains frequency (50/60 Hz); unstable or out-of-spec mains supply | no homeowner-safe action; this is a configuration/supply issue for a licensed technician; try a single reset if the code is resettable |
| E169 | Flue / air pressure switch fault (contact stays open) pro repair | blocked vent or excessive vent length; vent sagging / not sloped or supported correctly; low or fluctuating inlet gas pressure | check the outside flue terminal for visible obstruction (snow, debris) from a safe position; try a single reset if the code is resettable; if it recurs, call a licensed technician |
| E193 | Pre-circulation fault / circulation error (air or insufficient flow detected at startup; often self-clears) pro repair | air in the system; temporary low flow / poor circulation; low system pressure | check the pressure gauge and top up if low per the user manual; ensure system/radiator valves are open; try a single reset if the code persists |
Baxi boiler codes we get called for most
E133 — Ignition failure – no spark, no flame, or no flame signal (also covers interruption of gas supply / flame failure)
Typical causes include gas supply off, gas line not purged of air, or low gas pressure; faulty spark/ignition electrode or wiring; incorrect electrode spacing. A few things are safe to check yourself (confirm the gas supply is on and other gas appliances work; check the condensate drain is not blocked or frozen), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes E133 on Baxi boilers throughout Greater Vancouver.
E118 — Hydraulic (system water) pressure too low
Typical causes include low system pressure / water loss from a leak; air in the system or closed shutoff valve; expansion tank not correctly pressurized. A few things are safe to check yourself (read the pressure gauge; if low, top up via the filling loop per the user manual (typical target around 12-15 psi / ~1 bar cold); look for visible leaks around the boiler, pipework and radiators), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes E118 on Baxi boilers throughout Greater Vancouver.
E28 — Flue / heat exchanger NTC (flue high-limit) sensor fault
Typical causes include loose connection at the flue high limit and control board; short in the wiring harness; faulty flue sensor. A few things are safe to check yourself (press reset once if the code is resettable; if it recurs, call a licensed technician), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes E28 on Baxi boilers throughout Greater Vancouver.
E160 — Fan fault (fan not running at the correct speed or no fan feedback)
Typical causes include loose fan wiring at the fan or pcb connectors; seized or sticking fan; no supply voltage to the fan. A few things are safe to check yourself (try a single reset if the code is resettable; no internal access; call a licensed technician if it recurs), but the repair is a licensed, TSBC-certified gas technician job. HeatLand diagnoses and fixes E160 on Baxi boilers throughout Greater Vancouver.
Is it safe to keep running a Baxi boiler with a fault code?
Most Baxi fault codes put the boiler into a safe lockout for a reason. You can safely check the basics — gas supply on, power on, the thermostat calling for heat, system pressure in the normal range, and the condensate drain not frozen or blocked (a common cause in Vancouver cold snaps) — and restart it once. If the code returns, stop and book a technician. If you ever smell gas, leave the building and call your gas utility’s emergency line or 911 first. If a carbon-monoxide alarm sounds, get everyone out and call 911.
Baxi boiler repair across Greater Vancouver
HeatLand has kept Metro Vancouver homes comfortable since 1999. Our licensed, insured technicians diagnose and repair Baxi boilers — ignition faults, flame and sensor errors, low-pressure and pump problems, fan and flue faults, and control-board issues — including units we didn’t install. We’re brand-agnostic, carry common parts, and give you an honest repair-or-replace assessment with upfront pricing and a free estimate. If your boiler is beyond economical repair, we’ll show you right-sized, high-efficiency replacement options and the rebates available.
Need it sorted fast? We offer priority emergency boiler repair. Explore Boiler services, browse all boiler error codes by brand, or request a free estimate.
Baxi boiler service areas
We repair Baxi boilers across Greater Vancouver and the Fraser Valley, including:
Baxi boiler error code FAQs
Can I reset my Baxi boiler myself?
Yes — power-cycling the reset button once is generally safe after you’ve checked the basics (gas supply on, power on, the thermostat calling for heat, system pressure in the normal range, and the condensate drain not frozen or blocked (a common cause in Vancouver cold snaps)). If the boiler faults again right away, stop and note the code — repeatedly resetting a boiler that keeps locking out can mask a real problem. Call a licensed, TSBC-certified gas technician to diagnose it.
What does the Baxi E10 code mean?
On Baxi boilers, E10 commonly indicates outdoor temperature sensor fault (open or short circuit). Confirm the exact meaning against your unit’s manual — codes can vary by model and series — and have the repair done by a licensed, TSBC-certified gas technician. HeatLand fixes this across Greater Vancouver.
Do you repair Baxi boilers you didn’t install?
Yes. HeatLand is brand-agnostic and services Baxi boilers throughout Metro Vancouver and the Fraser Valley, whether or not we installed the unit. We carry common parts and give you an honest repair-or-replace assessment.
Is a Baxi boiler fault code an emergency?
No heat in cold weather is worth treating urgently. If you ever smell gas, leave the building and call your gas utility’s emergency line or 911 first. If a carbon-monoxide alarm sounds, get everyone out and call 911. For priority boiler repair across Greater Vancouver, call (604) 330-3812.
How much does Baxi boiler repair cost in Vancouver?
It depends on the fault. Many Baxi codes point to sensors, ignition or pump parts — usually far cheaper than replacement. We give upfront pricing and a free estimate before any work.
Baxi boiler acting up in Metro Vancouver? HeatLand’s licensed, TSBC-certified gas technicians diagnose and repair Baxi boilers across Greater Vancouver — including units we didn’t install.
Call (604) 330-3812Get a free repair estimateNo heat? Emergency repairMore Boiler error-code guides
HeatLand repairs every major boiler brand across Greater Vancouver. More brand guides:
Laars boiler codes
59 Laars boiler fault codes — meanings, causes & repair.
Burnham boiler codes
48 Burnham boiler fault codes — meanings, causes & repair.
Slant-Fin boiler codes
46 Slant-Fin boiler fault codes — meanings, causes & repair.
Triangle Tube boiler codes
46 Triangle Tube boiler fault codes — meanings, causes & repair.
Rinnai boiler codes
44 Rinnai boiler fault codes — meanings, causes & repair.
Buderus boiler codes
41 Buderus boiler fault codes — meanings, causes & repair.